JDHW-type explosion-proof infrared beam smoke detector

  • No:JDHW
  • Quantity:

      Recommend

    Explosion-proof infrared beam smoke detector JDHW-1.

    Product Description

    JDHW (to-shot) explosion-proof infrared beam smoke-sensitive fire detector (detector) is a line smoke-sensitive fire detector, suitable for installation at both ends of the protective space, a certain concentration of smoke alarm. This product can be used in places where smoke appears before the formation of a fire, especially suitable for large spaces, high racks, long-distance places. More responsive to black smoke. This product can be and any domestic and foreign manufacturers of fire alarm controller supporting the use, in line with the REQUIREMENTs of GB3836 series standards, through the national designated testing institutions, and achieved explosion-proof certificate.
    The detector consists of a pair of transmitters and receivers. The infrared beam emitted by the transmitter passes through the protective space, reaches the receiver, and the smoke from the combustion of the material diffuses to the beam area, so that the radiation flux received by the receiver weakens, and when the radiation flux weakens to a predetermined smoke-sensitive action threshold, the receiver outputs fire alarm information to the fire alarm controller. The detector receiver is equipped with six indicators indicating the strength of the signal for engineering commissioning.

    Technical parameters

    1, explosion-proof form: explosion-proof type
    2, explosion-proof logo: ExdIICT6
    3, operating voltage: DC15V to DC28V
    4, monitoring current: 12mA
    5, alarm current: s22mA
    6, the indicator: debug status: green and yellow light in a specific way always on or shining; normal monitoring status: red light flashing periodically; fire status: red light is always on, yellow light off; fault status: yellow light is always on, 20s after the detector to report fire, and the controller battery red light, Turn off the yellow light; the light path is completely blocked: the detector reports a fault and lights up
    7, protection area: maximum protection area 14x100 x 1400m2, maximum width 14m
    8, detection distance: 8m to 100m
    9, the use of the environment: temperature: -20 degrees C to 50 degrees C;
    10, inbound diameter: 2-M22x1.5 (the number and size of the inlet can be designed and produced according to user requirements)
    11, Weight: Transmitter: 2.5kg;