Home>Equipment list>Fire/emergency rescue equipment>Emergency alarm system>Monitoring Instrument OLCT20 for Fixed Ammonia
细节展示放大镜特效

Monitoring Instrument OLCT20 for Fixed Ammonia

  • No:OLCT20
  • Quantity:

      Recommend

    Monitoring Instrument OLCT20 for Fixed Ammonia

    probe

    OLCT 20

    OLCT 20D

    OLC 20

    type

    Explosion-proof transmitter

    Intrinsically safe transmitter

    Intrinsically safe probe

    Sensor type

    catalytic combustion/Electrochemistry

    Electrochemistry(OLCT 20D-catalytic combustion)

    catalytic combustion

    Detection of gases

    Combustible gas, poison gas, oxygen

    Toxic gas, oxygen

    Combustible gas

    Probe material

    INOX 316L Stainless steel

    Pre-calibration

    Yes

    Yes

    nothing

    Power Supply

    15 to 30 VDC(Catalysis)

    10 to 26 VDC

    Depending on the probe

    15 to 30 VDC(Electrochemistry)

    Maximum power consumption

    100 mA(Catalysis)

    25mA

    Depending on the probe

    25 mA(Electrochemistry)

    signal output

    4-20 mA

    4-20mA

    bridge type

    Load impedance

    250Ω (Catalysis)

    47Ω max

    nothing

    Depending on the power supply(Electrochemistry)

    Line system

    3Line (catalysis)

    2Line

    3Line

    2Wire (electrochemistry)

    Circuit impedance

    32Ω (Catalysis)

    (1km/1.5mm2)

    32Ω

    (1km/1.5mm2)

    32Ω

    (1km/1.5mm2)

    128Ω (Electrochemistry)

    (4km/1.5mm2)

    Connecting line

    When leaving the factory, attach a diameter of ____________6mmCable

    Electrical interface

    M25or3/4"NPT (OLCT 20D- With mounting bracket)

    M25or3/4"NPT (OLCT 20D- With mounting bracket)

    M25or3/4"NPT

    (OLC 20D- With mounting bracket)

    Protection Level

    IP 66

    Authentication

    EEx d IIC T6

    II 2 GD

    EEx ia IIC T4

    II 1 GD

    EEx d IIC T6

    II 2 GD

    INERIS 01 ATEX 0004X

    Chinese Type Certification 2003-C110 China Flameproof Certification Ex d IIC T6 China's intrinsic safety explosion-proof certification Ex ia IIC T4

    CEM Identification

    EN 50270

    weight

    800gram

    size(mm)

    L 130 x D 60

    L 130 x D 60

    L 130 x D 60

    working temperature

    -25 +60

    -25 +60

    -25°C to +70°C

    -25 °C to +200°C HTIn version