Testo310 portable flue gas analyzer
Product Name:Portable flue gas analyzer
Product type:Testo 310
First,Basic Functions and Applicable Places
1. On-site fast and reliable combustion equipment detection and combustion efficiency analysis;
2. It is a kind of equipment for measuring and analyzing flue gas under environmental conditions.
3. It is used to measure smoke environmental parameters of safety supervision and law enforcement or parameters of combustion equipment.
4. Easy to carry and use.
5. Safety supervision, supervision and application of law enforcement inspection;
6. Flue gas analysis and gas measurement of boilers or other combustion equipment or closed combustion environment.
Two.Characteristics and parameters
Characteristic:
1. Built-in four pilot menus: flue gas measurement, pumping force measurement, ambient CO measurement and differential pressure measurement;
2. Backlight design: large display with backlight, suitable for various lighting conditions;
3. Magnetic absorption design: The back of the instrument has magnetic absorption, which can be adsorbed on all metal surfaces, so that staff can freely handle other affairs with their hands.
4. Start-up auto-adjust to zero: Sensor start-up auto-adjust to zero, only 30 seconds;
5. Lightweight, strong and durable, dust-proof and impact-proof;
6. Built-in condensation tank can be quickly and easily cleared.
7. The measured data can also be directly transmitted to the testo infrared printer (optional) through the built-in infrared interface of the instrument, so as to realize on-site report printing.
8. The replacement of filter core is very simple.
Parameters:
Basic parameters: | ||||
Measurement items | range | accuracy±1 digit | Resolving power | Response time s |
Temperature (flue gas) | 0-400°C | ±1°C(0-100°C) ±1.5°C(greater than 100)°C) | 0.1°C | less than50s |
Temperature (environment) | -20-+100°C | ±1°C | 0.1°C | less than50s |
Pumping force value | -20-+20hPa | ±0.03 hPa(-3-+3 hPa) & Plussmn; 1.5% measured value (other ranges) | 0.01 hPa |
|
Pressure value | -40-+40 hPa | ±0.5 hPa | 0.1 hPa |
|
O 2 (Oxygen) | 0-21 Vol.% | ±0.2 Vol.% | 0.1 Vol.% | 30s |
CO (carbon monoxide) (none)HTamping compensation) | 0-4000ppm | ±20ppm(0-400 ppm) & plusmn; 5% measured value (401-2000 ppm) & plusmn; 10% measured value (2001-4000 ppm) | 1 ppm | 60s |
Environmental CO measurement | 0-4000ppm | ±20ppm(0-400 ppm) & plusmn; 5% measured value (401-2000 ppm) & plusmn; 10% measured value (2001-4000 ppm) | 1 ppm | 60s |
combustion efficiency | 0-120% | — | 0.1% | — |
Flue gas loss | 0-99.9% | — | 0.1% | — |
General technical parameters | ||||
Storage temperature | -20-+50°C | Operating temperature | -5-+45°C | |
display | Backlight four lines | Battery | Charging 1500 mA | |
Charger | 5V 1A | size | 201*80*44mm | |
weight | 700g | Memory card | nothing | |
Warranty and after-sale | 12 months |
Three.To configure
1. Portable flue gas analyzer mainframe (including rechargeable batteries);
2. Calibration report of O 2, CO, hPa and & deg; C;
3. 180 mm flue gas probe with fixed cone;
4. Silicone hose for pressure measurement;
5. 10 dust filter cores;
6. Instrument box.